AROUND THE
QUADS
Columbia
Dorms Meet or Exceed Fire Safety Codes By Shira
Boss
The deaths of
three Seton Hall University students in a dorm fire in January has
prompted a nation-wide examination of fire safety on college
campuses. Columbia administrators say that the school meets or
exceeds all fire safety regulations, but is reviewing its buildings
and policies to look for areas where improvement is needed and
taking steps to remedy weak spots already identified.
Main factors
in the Seton Hall deaths were reportedly lack of a sprinkler
system, which keeps exit routes open, and students not leaving the
building because they thought the alarm was false.
Four
dormitories on Morningside Heights - Carman, Hogan, Wien and
Woodbridge - do not have sprinklers in their hallways. They are
expected to be installed this summer at a cost of about $4 million,
as part of the annual summer program of building maintenance and
upgrading. Sprinklers are not required now, but a bill proposed in
the New York state senate would require their installation in all
campus dormitories within three years.
"We feel that
the dorms without sprinklers are safe, but an incident like Seton
Hall makes an institution like Columbia take a close look and make
sure we're doing everything in our power to make sure our students
are safe," says Michael Van Biema, executive director in the
office of administrative planning.
Because the
vast majority of alarms go off accidentally instead of for a real
fire, students at Columbia are also reluctant to dash out of the
building every time an alarm sounds. "I completely ignore fire
alarms these days," a Furnald Hall resident confessed to Spectator.
"I watch out my window to see if a crowd is gathering and people
are pointing and if so, I'll leave."
Last year
there were about 180 fire alarms in the University's 17 residence
halls. Nine of those went off because of an actual fire, and an
equal number were false alarms where the alarm was pulled for no
reason.
"We generally
get good compliance," with students evacuating buildings, Van Biema
contends. "Right now, because everyone's awareness has been
heightened [by the Seton Hall tragedy], we have better than
usual."
An e-mail
sent to students by Ross Fraser, director of residence
halls, following the Seton Hall fire emphasized that for their own
safety, students must leave the building whenever a fire alarm
sounds. Exceptions are for posted monthly alarm tests. Fraser said
that his office heard from students' parents wanting to know the
fire safety procedures and precautions in place at the
school.
Every dorm
room has either a smoke detector or heat detector that is wired
into a central alarm system and the fire department. Everyone is
required to leave the building and the fire department comes each
time a detector goes off. By special arrangement with the New York
City Fire Department, every alarm that goes off at Columbia is
responded to with three engine companies, two ladder companies and
a battalion chief - that amounts to about 32 fire fighters and six
vehicles. Alarms will ring continuously until inspected and
re-set.
Two of the
nine fires last year were from clothes dryers overheating and
igniting; the others were because of accidents like papers igniting
in a trash can, according to Joe McCormick Jr., assistant
director of the Office of Environmental Health and the university's
former fire safety officer. The largest cause of unwarranted alarms
is cooking smoke or steam, McCormick says.
"The quickest
response detector could be set off by hairspray or shower steam,"
he says. Near bathrooms, the university has changed to
photoelectric smoke detectors that are less sensitive to steam, and
in kitchens, heat detectors that measure a five-degree rise in heat
within 60 seconds are replacing traditional smoke
detectors.
The
construction of new or renovated dorms is class one fireproof,
which means walls and doors should contain a fire within a room for
an hour. Smoke, the leading cause of fire injuries, is not
prevented from spreading, however. The average response time by the
fire department is three to four minutes.
"Everything
is at least code compliant University-wide and is usually above and
beyond," McCormick says.
The most
recent serious fires were in John Jay Hall in 1996-97, McCormick
says. One was caused by an extension cord that overheated and
ignited the room; the other was ruled "suspicious" and may have
been set on purpose. In both cases the alarms worked and the fires
were contained to the rooms where they started.
Dorm policies
allow smoking in designated rooms. Some items that commonly cause
fires, like microwaves, hot plates, incense and candles, are
forbidden but often used anyway. (Candles may be used for religious
ceremonies or festivals with prior approval.)
A task force
has been formed to review the campus's residential policies, such
as allowing the use of halogen lamps, which can cause fires and are
currently discouraged, and will look for ways to improve fire
safety and student awareness of precautions.
Residential
advisors are supposed to review fire precautions with students at
the beginning of the school year, and many of them discuss fire
prevention issues at floor meetings during the school year.
McCormick frequently meets with student groups in dorms or those
who work in labs and other especially fire-prone areas to review
fire safety and sometimes practice using fire
extinguishers.
Last year,
about 150 students attended "An Evening with Fireman Joe," an event
in East Campus where McCormick discussed fire safety before and
after the screening of two movies, 1,000 Wings and
Backdraft.
|